Siemens
Building Technologies
4.1.3
Parameter setting
Start with quick commissioning according the commissioning guide
CM1G5192. It is very important to enter the right motor data!
Par. Nr.
Value
P0003
3
P0702(0)
26
P0702(1)
26
P1271(0)
For further information please see also Chapter 5 – Commissioning Wizard for
Essential Service Mode.
4.1.4
Remarks
• The hand mode will be disabled automatically when ESM is active.
• The information "drive fault" and "drive running" is still available on the 2 relay
outputs.
On demand the information "ESM active" can be configured to a relay output.
Application Guide «Fire Mode»
Application Examples
Parameter function
User access level 3
Function of DIN2 in Auto mode
Function of DIN2 in Hand mode
Activation of ESM control word
Function selection
Expert access
ESM
ESM
press▼ once;
will appear and ESM
control word is acti-
vated
15 / 44
CM1A5192en_01
23.10.2007