Parameter Setting; Remarks - Siemens SED2 Application Manual

Variable speed drive fire mode
Hide thumbs Also See for SED2:
Table of Contents

Advertisement

Siemens
Building Technologies
4.1.3

Parameter setting

Start with quick commissioning according the commissioning guide
CM1G5192. It is very important to enter the right motor data!
Par. Nr.
Value
P0003
3
P0702(0)
26
P0702(1)
26
P1271(0)
For further information please see also Chapter 5 – Commissioning Wizard for
Essential Service Mode.
4.1.4

Remarks

• The hand mode will be disabled automatically when ESM is active.
• The information "drive fault" and "drive running" is still available on the 2 relay
outputs.
On demand the information "ESM active" can be configured to a relay output.
Application Guide «Fire Mode»
Application Examples
Parameter function
User access level 3
Function of DIN2 in Auto mode
Function of DIN2 in Hand mode
Activation of ESM control word
Function selection
Expert access
ESM
ESM
press▼ once;
will appear and ESM
control word is acti-
vated
15 / 44
CM1A5192en_01
23.10.2007