Specifications - Siemens OpenAir GBB161.1U Technical Instructions

Electronic damper actuators, non-spring return, 24 vac, modulating control
Table of Contents

Advertisement

Technical Instructions
Document Number 155-176P25
June 22, 2015
Warning/Caution Notations

Specifications

Power supply
Control Signal
Feedback Signal
Equipment Rating
Auxiliary Features
Page 2
WARNING:
CAUTION:
Operating voltage (G–G0)
Frequency
Power consumption
Running...
Holding...
For one tandem application
of two actuators
Input signal (Y–G0)
voltage-input
Input resistance
Position output signal (U–G0)
Voltage-output
Maximum output current
Operating voltage, input signal and
position output signal
Plenum type actuators as a whole device
Dual auxiliary switches
AC rating (standard cable)
AC rating (Plenum cable)
DC rating (Standard/Plenum cable)
Switch Range
Switch A
Recommended range usage
Factory setting
Switch B
Recommended range usage
Factory setting
Switching hysteresis
WARNING:
Apply only AC-line voltage from the same phase or only UL-Class 2 voltage (SELV
for CE conformance) to the switching outputs of both auxiliary switches A and B.
Mixed operation is not permissible.
NOTE:
With plenum cables, only UL-Class 2 voltage (SELV for CE is
permissible).
GBB/GIB Series Non-spring Return, 24 Vac, Modulating Control
Personal injury/loss of life may occur if you do perform a procedure as
specified.
Equipment damage or loss of data may occur if you do not perform a
procedure as specified.
24 Vac ±20%
50/60 Hz
8 VA, 8W
1.1W
12 VA
0 to 10 Vdc
>100K ohms
0 to 10 Vdc
DC 1 mA
Class 2, in accordance with UL/CSA
Class 2, in accordance with UL/CSA
24 to 250 Vac
AC 6A resistive
AC 2A general purpose
24 Vac
AC 4A resistive
AC 2A general purpose
12 to 30 Vdc
DC 2A
0 to 90° with 5° intervals
0 to 45°
0 to 90° with 5° intervals
45 to 90°
85°
Siemens Industry, Inc.