Troubleshooting Table
Problem
Possible Cause
Low oil pressure shutdown.
Generator set
stops suddenly.
No fuel.
Overcrank shutdown.
Auxiliary winding circuit breaker tripped.
Fault shutdown.
Generator set in the OFF mode.
Remote stop command received from a remote
switch, ATS, or OnCuerPlus.
Generator thermostat tripped.
Engine malfunction.
Figure 5-3 General Troubleshooting
70
Section 5 Troubleshooting
Corrective Action
Check for oil leaks. Check the oil level and add oil if
necessary.
Check fuel valves and fuel supply.
Model 20RCA/20RCAL only: Check enclosure
thermostat and reset if tripped. See Section 5.5. Check
and clear air inlets and exhaust outlets.
Reset the controller. If the overcrank fault occurs again,
contact an authorized distributor/dealer.
Reset the auxiliary winding circuit breaker. Contact an
authorized distributor/dealer for service if breaker trips
repeatedly.
Check the controller display for fault messages. See
Section 2.5. Correct the fault condition and reset the
controller.
Press the RUN button to start the engine or press AUTO
to allow remote starting.
Check the remote switch position. Check OnCuerPlus.
Check for obstructed air inlets and outlets. Reset the
thermostat. See Section 5.5.
Contact an authorized distributor/dealer.