Connection To Electricity Supply - Wolf KGW Series Installation And Maintenance Instructions Manual

Standard air-conditioning units
Table of Contents

Advertisement

Connection to electricity
supply
KG 15
Mains
230V~
*Remove jumper if a room thermostat is connected
5-stage control
1 unit:
Switch: E5-3
2 units parallel:
Switch: E5-7
Switch type
E5-3
Voltage
230V
Current max.
3A
Weight
4.7 kg
Protection
IP 40

Connection to electricity supply

The air-conditioning unit must be wired by a trained, qualified electrician in
accordance with the applicable regulations (VDE, local power utility, etc.).
If the intake fan or discharge fan is switched off or fails, all control valves
must close automatically and the hot-water/cold-water and washer pumps
must shut down.
Install only control valves which are closed when de-energized and a frost-
protection thermostat without restart disabler.
Install a lockable repair switch for each drive motor to ensure that the air-
conditioning unit can be reliably shut down.
Completion of the electrical wiring work must be followed by a safety inspection
of the installation in accordance with VDE 0701 Part 1 and VDE 0700 Part 500 or
comparable national safety codes.
Caution
Use only electric motors designed to drive fans.
Always comply with the wiring diagram in the terminal box.
Use a thermistor-type trigger for a motor with PTC thermistor, an interlock
contactor for a motor with thermo-contacts, or a thermal overcurrent relay for a
motor without PTC thermistor or therm-contacts.
Fan
E5-7
230V
7A
8.5 kg
IP40
KG 20
Mains
230V~
* Remove jumper if a room thermostat is connected
H1 = Operation
H2 = Fault
5-stage control
1 unit:
Switch: E5-7T
2 units parallel:
Switch: E5-14T
Switch type
E5-7T
Voltage
230V
Current max.
7A
Weight
8.5 kg
Protection
IP 40
Fan with
thermo-contact
E5-14T
230V
14A
12.5 kg
IP20
13