Fujitsu AR 7 Installation Manual page 20

Slim duct type air conditioner indoor unit
Table of Contents

Advertisement

10.3.1. Function Details
Filter sign
Select appropriate intervals for displaying the fi lter sign on the
indoor unit according to the estimated amount of dust in the
air of the room.
If the indication is not required, select "No indication" (03).
Function
Setting
Number
Value
00
01
11
02
03
Static pressure
Select the appropriate static pressure according to the instal-
lation conditions.
Function
Setting
Number
Value
00
01
02
03
04
05
26
06
07
08
09
31
Range of static pressure is different by model.
Model Name
ARU7RLF
ARU9RLF
ARU12RLF
ARU18RLF
ARU24RLF
Auto restart
Enable or disable automatic restart after a power interruption.
Function
Setting
Number
Value
00
40
01
* Auto restart is an emergency function such as for power
outage etc. Do not attempt to use this function in normal
operation. Be sure to operate the unit by remote controller or
external device.
En-20
(♦... Factory setting)
Setting Description
Standard (400 hours)
Long interval (1000 hours)
Short interval (200 hours)
No indication
(♦... Factory setting)
Setting Description
0 in. WG (0 Pa)
0.04 in. WG (10 Pa)
0.08 in. WG (20 Pa)
0.12 in. WG (30 Pa)
0.16 in. WG (40 Pa)
0.20 in. WG (50 Pa)
0.24 in. WG (60 Pa)
0.28 in. WG (70 Pa)
0.32 in. WG (80 Pa)
0.36 in. WG (90 Pa)
0.1 in. WG (25 Pa)
[Standard]
Range of Static Pressure
0 to 0.36 in. WG (0 to 90 Pa)
0 to 0.2 in. WG (0 to 50 Pa)
(♦... Factory setting)
Setting Description
Enable
Disable
Room temperature sensor switching
(Only for Wired remote controller)
When using the Wired remote controller temperature sensor,
change the setting to "Both" (01).
Function
Number
42
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller
are active.
* Remote controller sensor must be turned on by using the
remote controller
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
Function
Number
44
External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function
Number
46
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller
only, change the setting to "Wired remote controller" (01). This
function will only work if the function setting 42 is set at "Both"
(01)
Function
Number
48
Setting record
 Record any changes to the settings in the following table.
Filter sign
Static pressure
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
After completing the Function Setting, be sure to turn off the
power and turn it on again.
(♦... Factory setting)
Setting
Setting Description
Value
00
Indoor unit
01
Both
(♦... Factory setting)
Setting
Setting Description
Value
00
A
01
B
02
C
03
D
(♦... Factory setting)
Setting
Setting Description
Value
00
Operation/Stop mode
01
(Setting prohibited)
02
Forced stop mode
(♦... Factory setting)
Setting
Setting Description
Value
00
Both
01
Wired remote controller
Setting
Setting Value