Refrigerant Thermistors - Daikin Comfora FTXP20~71L2V1B Service Manual

Split comfora r32 series
Table of Contents

Advertisement

2 Components
2.13.1

Refrigerant thermistors

Checking procedures
INFORMATION
It is recommended to perform the checks in the listed
order.
To perform a mechanical check of the specific thermistor
Prerequisite: Turn OFF the unit via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
work" on
page 35.
1 Locate the thermistor and remove the insulation if needed.
Check if there is thermal contact between the thermistor and
the piping or ambient.
Is the thermistor correctly
installed (thermal contact
between the thermistor and the
piping)?
Yes
No
To perform an electrical check of the specific thermistor
Prerequisite: First perform a mechanical check of the thermistor,
see
"Checking procedures" on
page 42.
1 Locate the thermistor.
2 Measure the temperature using a contact thermometer.
Name
Symbol
Location
(PCB)
Air
R1T
Main
thermistor
Heat
R2T
Main
exchanger
thermistor
Discharge
R3T
Main
pipe
thermistor
Heat
R2T
Indoor
exchanger
thermistor
INFORMATION
The thermistors may vary according to the specific unit.
3 Determine the thermistor resistance that matches the measured
temperature.
Type 1 thermistor
T °C
T °C
–20
197.81 10
39.96
Service manual
42
"2.10  Plate
Action
Perform an electrical check of the
specific thermistor, see
"Checking procedures" on
page 42.
Correctly install the thermistor,
see
"Repair procedures" on
page 43.
Connector
Type
(pins)
S90:1‑2
1
S90:3‑4
1
S90:5‑6
1
S32:1‑2
1
T °C
T °C
40
10.63
70
3.44
T °C
T °C
–19
186.53
11
38.08
–18
175.97
12
36.30
–17
166.07
13
34.62
–16
156.80
14
33.02
–15
148.10
15
31.50
–14
139.94
16
30.06
–13
132.28
17
28.70
–12
125.09
18
27.41
–11
118.34
19
26.18
–10
111.99 20
25.01
–9
106.03
21
23.91
–8
100.41
22
22.85
–7
95.14
23
21.85
–6
90.17
24
20.90
–5
85.49
25
20.00
–4
81.08
26
19.14
–3
76.93
27
18.32
–2
73.01
28
17.54
–1
69.32
29
16.80
0
65.84
30
16.10
1
62.54
31
15.43
2
59.43
32
14.79
3
56.49
33
14.18
4
53.71
34
13.59
5
51.09
35
13.04
6
48.61
36
12.51
7
46.26
37
12.01
8
44.05
38
11.52
9
41.95
39
11.06
4 Disconnect the thermistor connector from the appropriate PCB.
5 Measure the resistance between the appropriate pins of the
thermistor connector.
6 Check that the measured resistance value matches the
resistance determined through the measured temperature
(earlier step in the procedure). E.g. R1T thermistor:
▪ Measured temperature with contact thermometer: 23.1°C,
▪ Resistance value determined through temperature (using the
table for type 1 thermistors):
Resistance at 23°C: 21.85 kΩ,
Resistance at 24°C: 20.90 kΩ,
▪ Disconnect connector and measure resistance between S90
pin 1‑2:
Measured resistance: 21.86 kΩ,
▪ Measured resistance value is inside the range. R1T
thermistor passes the check.
INFORMATION
All thermistors have a resistance tolerance of 5%.
INFORMATION
The user interface allows to monitor most thermistors.
If the measured resistance value matches the resistance
determined through the measured temperature, but the
temperature for the corresponding thermistor is NOT
correct on the user interface display, replace the applicable
PCB.
ATXP20~35L2V1B + FTXP20~71L2V1B + ARXP20~35L2V1B +
T °C
T °C
41
10.21
71
3.32
42
9.81
72
3.21
43
9.42
73
3.11
44
9.06
74
3.01
45
8.71
75
2.91
46
8.37
76
2.82
47
8.05
77
2.72
48
7.75
78
2.64
49
7.46
79
2.55
50
7.18
80
2.47
51
6.91
52
6.65
53
6.41
54
6.65
55
6.41
56
6.18
57
5.95
58
5.74
59
5.14
60
4.87
61
4.70
62
4.54
63
4.38
64
4.23
65
4.08
66
3.94
67
3.81
68
3.68
69
3.56
RXP20~71L2V1B
Split Comfora R32
ESIE18-01 – 2019.02