4
Mechanical setup of the sample station
The setup of the sample station is divided into two steps. First, the setup of
the power supply and the CPU is explained. After becoming acquainted
with the analog module SM331 the mounting of it is described.
4.1
Mounting the sample station
Before you can use the analog input module SM331, you need a basic
setup of general SIMATIC S7-300 components.
The order of the mounting takes place from left to right:
• Power supply PS307
• CPU 315-2DP
• SM331
Table 4-1
Graphics
Mounting the sample station (without SM331)
Description
Bolt together the rail to the ground or underground (screw
size: M6) so that at least 40 mm space remains above and
below the rail
If the base is a grounded sheet metal or a grounded
mounting plate, ensure that the rail and the base are con-
nected together with low resistance.
Connect the rail with the protective ground wire. A M6 bolt
is available for this purpose.
Mounting the power supply
• Hang the power supply to the top end of the rail
•
and tighten it to the rail underneath
8
Getting Started SM331 AI 8x12bit Part1: 4-20mA
A5E00253410