11.7 External Trip Initiation

11.7
External Trip Initiation
Setting Values
Tripping delay
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Tolerance
Sequence tolerance for delay times
35
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
Outputs
1120
0.00 s to 60.00 s
Approx. 10 ms + OOT
35
.
1 % of the setting value or 10 ms
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
Increments of 0.01 s