Download Print this page

Procedure To Remove Electronic Expansion Valve And Low Pressure Sensor - Daikin R125LUY1 Service Manual

3/4/5/6 hp class
Hide thumbs Also See for R125LUY1:

Advertisement

Si241312
6. Procedure to Remove Electronic Expansion Valve
and Low Pressure Sensor
Procedure
Step
Removing the parts of
outside panel and the
switch box according to
the "Procedure to
Remove Outside Panels".
1. Removing electronic
expansion valve
Pull up the electronic
1
expansion valve coil.
2
To remove the
electronic expansion
valve, disconnect 2
brazed joints for each
valve.
2. Removing the low
pressure switch
Disconnect 1 brazed
1
joint to remove the low
pressure switch.
Removal Procedure

Procedure to Remove Electronic Expansion Valve and Low Pressure Sensor

Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Points
Check that the refrigerant is
completely discharged
before starting the
disassembling work.
Electronic
expansion
valve coil
Cover the other piping with
Electronic
sheet for welding work or
expansion
valve
steel sheet to prevent the
piping from influence of torch
Low
flame.
pressure
switch
Caution
When installing, use torch
flame while cool the valve
body with wet cloths or the
like to keep it below 120°C.
7