Installing An Ethernet Switch (Modular) Fn2012; Installation Of Ethernet Modules - Siemens FS20 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installation of the compact control panels
5

Installing an Ethernet switch (modular) FN2012

5.16 Installing an Ethernet switch (modular) FN2012

5.16.1 Installation of Ethernet modules

142 | 354
Building Technologies
Fire Safety
Malfunctions during a partial upgrade
Ethernet switch (modular) FN2012 is not compatible with Ethernet switch (MM)
FN2008 and so may only be used in panels ≥MP6.
The Ethernet switch (modular) must be equipped with Ethernet modules.
Installation is the same for all modules.
Figure 69: Installation of an Ethernet module in the Ethernet switch (modular)
1
Ethernet switch (modular)
2
Ethernet module built-in
3
Fixing screw with retaining spring
4
Ethernet module
5
Plug-in contacts
6
Threaded fixing hole
7
Positioning aid
1. Position the Ethernet module (4) as shown.
2. Push the Ethernet module (4) into the slot opening so the plug-in contacts (5)
slide into the connector on the Ethernet switch.
3. Ensure that the Ethernet module (4) slides into the positioning aids (7).
4. Use the fixing screw (3) to fix the Ethernet module in the threaded hole (6).
5. Wire up the Ethernet module according to chapter 'Wiring'.
7
6
5
1
2
3
4
008851_s_en_--