PDU plugs, circuit breakers, and receptacles
The PDU plugs must be appropriate for the power sources at the installation sites. The
following table lists the plugs on the end of the PDU power cords. The power distribution
panel at the installation site must have receptacles that match these plugs.
Required number of plugs in each PDU per chassis:
Controller chassis: 4
■
Drive chassis:
■
SFF: 16
●
LFF: 16
●
FMD: 8
●
Required number of PDUs per rack:
Controller rack:
■
Single phase: 4
●
Three phase: 2
●
Drive rack:
■
Single phase: 4
●
Three phase: 2
●
Data center requirements
The data center must meet the following requirements. Detailed mechanical, electrical,
and environmental requirements are listed in the following table.
Item
General
Temperature
Humidity
ESD
Electrical
interference
Hitachi Virtual Storage Platform G1000, G1500, and VSP F1500 Hardware Guide
Table 13 Data center requirements
The data center must provide appropriate power, air
conditioning, cabling, and fire protection.
The data center must maintain ambient temperature from 50ºF
(10ºC) to 95ºF (35ºC).
The data center must maintain ambient humidity from 20% to
80%, noncondensing.
The data center must provide adequate protection from
electrostatic discharge (ESD).
The data center must provide adequate protection from
electrical/radio frequency interference.
Chapter 4: Site preparation specifications
Data center requirements
Description
81