3.1.4

Lifting

WARNING
Heavy equipment handling! Personal injuries! Never stay in the
surrounding area when the unit is lifted. Use only adequate tools and fastening
devices to secure the unit during transport and lifting.
CAUTION
Incorrect handling! Unit damage! Never use slings for transport or lifting as
they would squeeze the unit.
Always lift the unit by points marked with yellow arrows on pictures below.
Figure 25: Lifting points in OMTE & OLTE units

Figure 26: Centre of gravity

3.2

Electrical connection

3.2.1

Power supply connections

WARNING
Electrical shock hazard! Serious personal injuries! There are unused fast-
on pins on the XCM25D which could be under voltage. They are covered by
insulated fast-on flags in the factory. Handle carefully when removing insulating
flags during service on site.
The electrical connection of the refrigeration unit to the power supply must be made by qualified
technicians in compliance with the valid electrical standards, eg, DIN EN 60204-1.
Additionally, the voltage drop and temperatures must be considered for cable selection.
Copeland EazyCool Large Outdoor OMTE & OLTE condensing units are designed for a 380-420V /
3Ph / 50 Hz power supply. A voltage tolerance of ± 10% is acceptable.
The circuit breaker must be switched off before opening the front door.
C6.1.9/0219/E