Remote Display Ccm60; Figure 13: Remote Display Front Panel Mounting - Emerson Copeland Eazycool OMTE-90D-TFD Application Manuallines

Large outdoor condensing unit
Table of Contents

Advertisement

LED
Mode
On
On
On
Table 8: LED functions description
NOTE: By default, the local display will show the value of the suction pressure during
operation. This can be changed by choosing another value for parameter B03 (Remote
Display visualization).
Setting for
Value shown on the display
B03
0
P1 value = Suction pressure
1
P2 value = Mid-coil temperature (condenser)
2
P3 value = Discharge line temperature
3
P4 value = nu
4
P5 value = Liquid switch
5
P6 value = Ambient temperature
6
P7 value = Rescue mode
7
PEr value = Probe error
8
Aou value = Analog output
Table 9: Display visualisation
2.9.2

Remote display CCM60

This device allows for remote monitoring and control of the XCM25D controller via cable. The CCM60
has the same interface as the unit controller therefore the commands and symbols are identical to
those of the XCM25D controller. The remote display shall be mounted on a vertical panel, in a 29 x
71 mm hole, and secured using the special bracket supplied (see Figure 13).
The temperature range allowed for correct operation is 0°C to +60°C.
Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. Allow for air to
circulate through the cooling holes.
When front mounted the remote display is IP65 rated.

Figure 13: Remote display front panel mounting

The remote display is a proprietary bus of communication for Dixell HMI (x-rep, CCM60) interfaces.
There are two connection terminals on the back of the remote display (+ and -).
NOTE: Emerson recommends using a shielded cable twisted pair 2 x 0.5mm².
14
Function
Digital unloader solenoid On
In defrost
Evaporator fans - Liquid line solenoid valve On
Comments
Not available
Not available
C6.1.9/0219/E