Electrical Specifications for the Sun Fire E4900 System
TABLE 3-4
Parameter
Input current
Voltage range
Current, maximum
Current frequency range
Input power rating
Total continuous power
Volt-Ampere rating
Btu rating
Power factor
Connector type
North American
International
Receptacle type
North American
* One power cord for each power supply installed. Minimum required is two and maximum is three.
\ One receptacle type for each power cord installed.
Electrical Specification for the Sun Fire Cabinet (Empty)
TABLE 3-5
Parameter
Input current
Voltage range
Current, maximum
Current frequency range
Volt-Ampere
rating
North American
Connector type
International
Receptacle type
North American
* One power cord for each RTS installed. Minimum required is one and maximum is four.
\ One receptacle type for each power cord installed.
Value
200-240 VAC
20A at 230 VAC for each power cord
(2+1 redundancy)
47-63 Hz
4508W
4600 VA
15380 Btu/hr
0.98 (with Sun Products)
3 - NEMA 6-15P for 200–240 VAC
3 - 10A, single-phase IEC 320, for 200–240
1
VAC
3 - NEMA 6-15R for 200–240 VAC
Value
200-240 VAC
24A at 208 VAC for each RTU
47-63 Hz
4,992 VA
NEMA L6-30P for 200–240 VAC
32A, single-phase IEC 309, for 200–240
1
VAC
NEMA L6-30R for 200–240 VAC