Planning Your Access Route - Sun Microsystems Sun Fire E6900 Site Planning Manual

Systems
Hide thumbs Also See for Sun Fire E6900:
Table of Contents

Advertisement

2.3

Planning Your Access Route

If your existing loading dock meets height or ramp requirements for a standard
freight carrier truck, you can use a pallet jack to unload the system. If not, you must
provide a standard forklift
system be shipped in a truck with a lift gate.
See
FIGURE 2-4
Each system is shipped in a separate crate. A pallet jack is required to move each
shipping crate to the system location.
Leave each system in its shipping crate until it reaches its final destination. If the
crate does not fit through the planned access route, partially disassemble it.
All systems not shipped in a cabinet should only be lifted by proper computer-lifting
equipment to prevent personal injury and/or damage to system equipment.
The entire access route to your computer room should be free of raised patterns that
can cause vibration, and the route must meet the following requirements:
TABLE 2-5
Minimum door height
Minimum hallway and door width
Minimum elevator depth
Maximum incline
TABLE 2-6
Minimum elevator, pallet jack, and floor loading capacity
(maximum weight per system)
1. A standard forklift has a maximum outside tine dimension of 27 in. (69 cm) and a minimum inside tine
dimension of 15 in. (38 cm).
1
or other means to unload the system, or request the
for an illustration of the system shipping crate and its dimensions.
Access Route Clearance
Weight Requirements
With Shipping Pallet
81 in. (205 cm)
44 in. (112 cm)
65.5 in. (166 cm)
10°
Chapter 2 Physical Specifications
Without Shipping Pallet
75 in. (190.5 cm)
25 in. (64 cm)
61 in. (155 cm)
10°
1200 lbs (544 kg)
2-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun fire e4900

Table of Contents