Emerson FB2100 Flow Computer Instruction Manual
D301783X012
March 2019
5.4
Removing/Replacing the HMI Module
You do not need to power down the unit to remove/replace the HMI module if you are in a non-
hazardous area.
DANGER
Ensure the flow computer is in a non-hazardous area. Never remove/replace the HMI module in a
hazardous area.
Important
The HMI module includes the Wi-Fi transceiver; once you remove the HMI module; Wi-Fi
communication with the flow computer ceases.
1.
2.
3.
84
Open the enclosure.
Loosen the four captive fastening screws on the HMI module.
Figure 5-4. Captive Fastening Screws
Grasp the HMI module and remove it by gently pulling it straight out away from the unit.
Service and Troubleshooting