Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aoya09Klwa And Aoya12Klwa - Fujitsu ASYA09KLWA Design & Technical Manual

Wall mounted type
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Models: AOYA09KLWA and AOYA12KLWA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Height difference H (m)
Height difference H (m)
6-1. Models: AOYA09KLWA and AOYA12KLWA
Height difference H
1
*
H
Outdoor unit
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
- 26 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
5
10
10
0.973
5
0.995
0.983
0
1.000
0.988
-5
1.000
0.988
-10
0.988
Pipe length (m)
5
10
10
0.993
5
1.000
0.993
0
1.000
0.993
-5
0.992
0.985
-10
0.977

6. Capacity compensation rate for pipe length and height difference

2
*
20
25
0.948
0.936
0.958
0.945
0.963
0.950
0.963
0.950
0.963
0.950
20
25
0.978
0.970
0.978
0.970
0.978
0.970
0.970
0.962
0.962
0.955