Control via the operator panel
5.5 Menu commissioning / service
Battery symbol
In this menu, the battery symbol can be activated so that it is displayed in the operating
screen form. When the display is activated, then the battery symbol is shown instead of the
time of day seconds display. It displays the battery voltage in 20 % steps. If the display was
received in the last 20 %, then the battery symbol flashes in order to indicate that the battery
must be replaced.
Battery symbol (factory setting: NO)
● Yes: The battery symbol is shown at the top right of the operating screen form - at the
time of day seconds display.
● No: The battery symbol is not displayed in the operating screen form.
5.5.5

AOP diagnostics

Software/database version
You can use this menu to display the firmware and database versions.
The database version must be compatible with the drive software status (you can check this
in parameter r0018).
Database contents
For service purposes, the contents of the database are displayed in the screen form.
Battery status
In this menu, you can display the battery voltage numerically (in Volts) or as a bar display.
The battery ensures that the data in the database and the current time are retained.
When the battery voltage is represented as a percentage, a battery voltage of ≤ 2.30 V is
equal to 0%, and a voltage of ≥ 3 V to 100%.
The data is secure up to a battery voltage of 2.30 V.
● If the battery voltage is ≤ 2.45 V, the message "Battery weak - replace soon" is displayed
in the status bar.
● If the battery voltage is ≤ 2.30 V, the system displays the following message: "Battery
defect - replace immed."
● If the time and/or database are not available after the system has been switched off for a
prolonged period due to the voltage being too low, the loss is established by means of a
CRC check when the system is switched on again. This triggers a message instructing
the user to replace the battery and then load the database and/or set the time.
For instructions on how to change the battery, see "Maintenance and servicing".