Technical data of CPU 31xC
6.4 CPU 313C-2 PtP and CPU 313C-2 DP
Technical data
Functionality
MPI
PROFIBUS DP
Point-to-point connection
MPI
Services
PG/OP communication
Routing
Global data communication
S7 basic communication
S7 communication
As server
As client
Transmission rates
2nd interface
Type of interface
Physics
electrically isolated
Interface power supply (15 to 30 VDC)
Number of connections
Functionality
MPI
PROFIBUS DP
Point-to-point connection
DP master
Number of connections
Services
PG/OP communication
Routing
Global data communication
S7 basic communication
S7 communication
Constant bus cycle time
SYNC/FREEZE
Enable/disable DP slaves
DPV1
Transmission rates
Number of DP slaves per station
Address area
User data per DP slave
6-18
CPU 313C-2 PtP
Yes
No
No
Yes
No
Yes
Yes
Yes
No (but via CP and loadable FBs)
Max. 187.5 kbps
Integrated RS422/RS485 interface
RS 422/485
Yes
No
None
No
No
Yes
CPU 313C-2 DP
Yes
Integrated RS485 interface
RS 485
Yes
Max. 200 mA
8
No
Yes
No
8
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Up to 12 Mbaud
Max. 32
Max. 1 KB I / 1 KB O
Max. 244 bytes I / 244 bytes O
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06