In Bypass mode, the load accepts the power not from the pure power outputted by the inverter, but from the mains
power directly.
For the detailed information of the Normal mode, Bypass mode, Battery and Maintenance Bypass mode, please refer to
section 1.5 UPS State and Operation Mode.

5.4.1 Transfer from Bypass Mode to Inverter Mode

In Bypass mode, press and hold the power button.
If the ECO mode is not turned on, the interface shown in Figure 5-4 will appear.
Figure 5-1 ECO Mode not turned on
Select 'Turn on UPS' and click OK to transfer to the Inverter mode, see Figure 5-5.
Select 'Turn off UPS' and click OK to shut down the UPS output.
Vertiv|Liebert® S600 10kVA ~ 20kVA UPS | User Manual
59