Input Modify To Linear (4~20Ma) - Taie FY400 Operation Manual

Digital temperature controller
Hide thumbs Also See for FY400:
Table of Contents

Advertisement

15.3

Input modify to Linear (4~20mA)

Plug 2 pcs of Jumper in the right slot as shown
Linear analog signal (4~20mA) calibration flowchart
FY/FU operation manual
Jumper Position
Start
SET 2_2 = 1
ANL1 = 0
ANH1 = 5FFF
DP = 0000
INP1 = AN4
USPL = 5000
LSPL = 0
Input analog signal 4mA
Adjusts "ANL1" until PV = 0
Input analog signal 20mA
Adjusts "ANH1" until PV = 5000
Input 4mA Check the PV = 0 Input
20mA Check the PV = 5000
NO
OK ?
YES
Repeat step A~E 3~4 times
NO
OK ?
YES
End
Set the range you want
Ex: Low = -10.0, High = 10.0
Set LSPL = -10.0, USPL = 10.0, DP : 000.0
Software Setting
Parameter set as "INP1=AN4"
to display ANL1 & ANH1 & DP
at Input level (level 3)
Step A
Step B
Step C
Step D
Step E
58

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fy600Fy700Fu400Fy900Fu48Fu86 ... Show all

Table of Contents