Input Modify To Rtd - Taie FY400 Operation Manual

Digital temperature controller
Hide thumbs Also See for FY400:
Table of Contents

Advertisement

15.2

Input modify to RTD

Plug 2 pcs of Jumper in the left slot as shown
57
Jumper Position
RTD calibration flowchart
Start
SET 2_2 = 1
ANL1 = 0
ANH1 = 5FFF
INP1 = PT1
USPL = 850.0
LSPL = -199.9
Input PT100 signal -199.9°C
Adjusts "ANL1" until PV = -199.9
Input PT100 signal 850.0°C
Adjusts "ANH1" until PV = 850.0
Input -199.9°C Check the PV = -199.9
Input 850.0°C Check the PV = 850.0
NO
OK ?
YES
Repeat step A~E 3~4 times
NO
OK ?
YES
End
Set the range you want
Ex: Low = 0.0 , High = 200.0
Set LSPL = 0.0 , USPL = 200.0
Software Setting
Parameter set as"INP1=PT1~PT3"
to display ANL1 & ANH1 & DP
at Input level (level 3)
Step A
Step B
Step C
Step D
Step E
FY/FU operation manual