Step 5: Verify Configuration - Emerson Rosemount 2051CF Series Quick Installation Manual

Pressure transmitter with foundation fieldbus/flowmeter transmitter with foundation fieldbus
Hide thumbs Also See for Rosemount 2051CF Series:
Table of Contents

Advertisement

Rosemount 2051
S
5: V
TEP
ERIFY
Each Foundation fieldbus host or configuration tool has a different way of displaying and
performing configurations. Some use Device Descriptions (DD) or DD methods for
configuration and to display data consistently across platforms. There is no requirement that
a host or configuration tool support these features. Use the following block examples to do
basic configuration to the transmitter. For more advanced configurations see the 2051
reference manual (document number 00809-0200-4101).
NOTE
DeltaV users should use DeltaV Explorer for the Resource and Transducer blocks and
Control Studio for the Function Blocks.
To configure the AI Block
AI Block configuration parameters
Use the Pressure, DP Flow, and DP Level examples for guides.
Parameters
Channel
L_Type
XD_Scale
Note: Only select the units that are supported by the device.
Out_Scale
Pressure example
Parameters
Channel
L_Type
XD_Scale
Note: Only select the units that are supported by the device.
Out_Scale
DP Flow example
Parameters
Channel
L_Type
XD_Scale
Note: Only select the units that are supported by the device.
Out_Scale
10
C
ONFIGURATION
Enter Data
1 = Pressure or 2 = Sensor Temp
Direct, Indirect, or Square Root
Scale and Engineering Units
Pa
bar
inH20 @ 68°F
kPa
mbar
mmH20 @ 68°F
torr
atm
ftH20 @ 68°F
Scale and Engineering Units
Enter Data
1
Direct
See list of supported engineering units.
Set values outside operating range.
Enter Data
1
Square Root
0 - 100 inH
0 @ 68°F
2
0 - 20 GPM
Quick Installation Guide
00825-0200-4101, Rev EA
psi
inHg @ 0°C
g/cm2
mmHg @ 0°C
kg/cm2
mmH20 @ 4°C
inH20 @ 4°C
June 2010