Siemens Simatic S7-1500R System Manual page 106

Redundant system
Hide thumbs Also See for Simatic S7-1500R:
Table of Contents

Advertisement

Installing a system power supply
To install the system power supply, follow these steps:
1. Insert the U-connector into the back of the system power supply.
2. Hang the system power supply on the mounting rail.
3. Swivel the system power supply to the rear.
Figure 4-5
4. Open the front cover.
5. Disconnect the power cable connector from the system power supply.
6. Screw the system power supply tight (torque 1.5 Nm).
7. Insert the already wired-up power cable connector into the system power supply.
Information on wiring the power cable connector is available in the section Wiring the system
power supply and load power supply (Page 117).
Uninstalling a system power supply
The system power supply is wired up.
To uninstall the system power supply, follow these steps:
1. Open the front cover.
2. Shut down the system power supply.
3. Turn off the supply voltage.
4. Disconnect the power cable connector, and remove the connector from the system power
supply.
5. Unscrew the fixing screw.
6. Swivel the system power supply out of the mounting rail.
S7-1500R/H redundant system
System Manual, 10/2018, A5E41814787-AA
Installing a system power supply
4.4 Installing a system power supply
Installation
105