Fitting The Cover; Connections On The Heating Water Side - Viessmann VITOCELL 300-W Installation Instructions And Setup Manual

Dhw cylinder with internal indirect coil
Table of Contents

Advertisement

500 l capacity
(cont.)

Fitting the cover

A
2.
Fig. 12
Cap with Viessmann logo
A

Connections on the heating water side

Connect all pipework with detachable fittings.
Seal any connections that are not required with red
brass caps.
Adjust the temperature controller and high limit
safety cut-out so that the DHW temperature in the
DHW cylinder does not exceed 95 °C.
For 160, 200 and 300 l and heating water flow tem-
peratures above 95 °C:
Remove the pipe collars from the pipe outlets on the
heating water side (pipe collars have l.h. threads).
!
Please note
The internal indirect coil is installed with gas-
kets.
Temperatures > 150 °C at the connections will
damage the gaskets.
Maintain a safe distance when soldering and
welding.
Realigning the connector will damage the gas-
kets.
1.
Note
The soft side of the thermal insulation must rest
against the cylinder body.
Permissible temperature
Permissible operating
pressure
Test pressure
Individual cylinder
160 °C
10 bar (1.0 MPa)
16 bar (1.6 MPa)
15