Fitting The Thermometer Sensor (If Supplied) And Cylinder Temperature Sensor - Viessmann VITOCELL 300-W Installation Instructions And Setup Manual

Dhw cylinder with internal indirect coil
Table of Contents

Advertisement

500 l capacity
(cont.)

Fitting the thermometer sensor (if supplied) and cylinder temperature sensor

1.
Fig. 9
1. Guide the thermometer sensor through the cover
strip and insert the thermometer.
Note
The cover strip is held in its vertical position by the
straight capillaries. This is necessary for the rest of
the installation.
2. Insert the upper thermometer sensor as far as it
will go into the hole in the cylinder cap.
3. Use clips to secure the thermometer sensor
against being pulled out.
4. Route the bottom thermometer sensor capillaries
to the back of the cylinder body.
5. Screw the nuts onto the threaded studs. Do not
tighten.
12
3.
2.
4.
6.
A
6. Slot the clamps onto the threaded studs and align.
7. Tighten the nuts.
8. Depending on where the sensor is being fitted:
Insert the thermometer sensors and cylinder
temperature sensors into clamp
will go.
Note
Never wrap insulating tape around the sensors.
When the thermal insulation is being fitted, the
cylinder temperature sensor leads are routed
outwards through the apertures (slots) in the rear
cover strip.
5.
7.
8.
as far as they
A