10. Appendix 2 Setting the Tag Data Links Using the Software
10.3.2. Setting the Global Variables
Set the global variables to use for the tag data links.
1
Double-click Global Variables
under Programming - Data in
the Multiview Explorer.
2
The Global Variables Tab Page
is displayed in the Edit Pane.
Click a column under the Name
Column to enter a new variable.
Enter EIP002_D10100_OUT in
the Name Column.
Enter WORD[10] in the Data
Type Column.
*After entering, the value
changes to ARRAY[0..9] OF
WORD as shown on the right.
Select the Retain Check Box to
retain the value.
Select Output from the Network
Publish Menu.