Significance Of The Leds For The Voltage Sensing Module Vsm10 - Siemens Sinamics G130 Operating Instructions Manual

Voltage sensing module 10 (vsm10)
Hide thumbs Also See for Sinamics G130:
Table of Contents

Advertisement

Electrical installation
4.3 Interface description
4.3.8

Significance of the LEDs for the Voltage Sensing Module VSM10

Table 4- 7
Description of the LEDs on the Voltage Sensing Module
LED
Color
READY
---
Green
Orange
Red
Green/red
Green/orange
or
red/orange
24
Status
OFF
The electronics power supply is missing or lies outside the permissible
tolerance range.
Continuous light The component is ready for operation and cyclic DRIVE-CLiQ communi-
cation is taking place.
Continuous light DRIVE-CLiQ communication is being established.
Continuous light This component has at least one fault.
Remark:
The LED is activated irrespective of whether the corresponding messag-
es have been reconfigured.
Flashing 0.5 Hz
Firmware is being downloaded.
Flashing 2 Hz
Firmware download is complete. Waiting for POWER ON.
Flashing light
Detection of the components via LED is activated (p0144).
Remark:
Both options depend on the LED status when module recognition is
activated via p0144 = 1.
Description
Voltage Sensing Module 10 (VSM10)