Fisher N551 Instruction Manual

Fisher N551 Instruction Manual

Snappy joe emergency shutoff valves

Advertisement

Quick Links

Instruction Manual
September 2015
Types N551 and N851 Snappy Joe
Shutoff Valves
WARNING
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or fire
causing property damage and personal injury
or death.
Fisher
equipment must be installed,
®
operated and maintained in accordance
with federal, state and local codes
and Emerson Process Management
Regulator Technologies, Inc. (Emerson™)
instructions. The installation in most
states must also comply with NFPA No. 58
or ANSI K61.1 standards.
Only personnel trained in the proper
procedures, codes, standards and
regulations of the LPG or anhydrous
ammonia (NH
) industries should install and
3
service this equipment.
Introduction
Scope of the Manual
This manual provides installation and maintenance
instruction for the Types N551 and N851 Emergency Shutoff
Valves and Accessories.
Description
Type N551 Snappy Joe (Figure 1) emergency shutoff valve is
UL
Listed for service in Propane or Anhydrous Ammonia (NH
®
Type N851 emergency shutoff valve is intended for all other
compressed gas service. Reference to Type N551 also refers to
Type N851 unless otherwise specified.
UL
®
is a mark owned by Underwriters Laboratories.
The valves may be installed on both ends of transfer hoses
where the hose connects the bulk plant piping to the bobtail,
transport or tank car. They provide a quick way of shutting
off gas flow in the event of a hose rupture and meet the
requirements for such service when correctly installed with
a remote release and proper piping support. The Type N551
valve is lever operated, latch-open and quick closing valve. A
fusible element in the latch melts if the temperature reaches
212°F / 100°C, allowing the valve to close.
The following accessories are also covered:
Type P164B – Cable Release Assembly
).
3
Type P327D – Remote Pneumatic Release Assembly
www.fisherregulators.com
Types N551 and N851
Emergency
Figure 1. Type N551 in Closed Position

Advertisement

Table of Contents
loading

Summary of Contents for Fisher N551

  • Page 1 Types N551 and N851 Emergency Shutoff a remote release and proper piping support. The Type N551 Valves and Accessories. valve is lever operated, latch-open and quick closing valve. A...
  • Page 2: Operation

    Types N551 and N851 Specifications The Specifications table lists specifications for the Types N551 and N851 valve which is designed for butane, propane or NH service at ambient temperatures. Contact your local Sales Office if the valve is to be used on any other service, fluid, compressed gas or temperature condition.
  • Page 3: Cable Hook-Ups

    A fusible element that will close the Type N551 shall be located release point over pulleys or through conduit. Adjust the cable within five feet of the hose connection. If the Type N551 is placed so that minimal pull is required to close the emergency valves.
  • Page 4 To install the Type P327D, see Figure 4: the handle set screw to secure the handle to the inner cable. 1. Close the Type N551 valve. Handle is parallel to the pipe. 2. Remove the long end of the external spring from CAUTION under the latch block.
  • Page 5 Type N551’s operating handle to the truck along the transfer hose(s). This cable would close the valve if the hose(s) is stretched (driver does not disconnect) beyond a preselected CAUTION limit.
  • Page 6: Maintenance

    “S” HOOK IN. / mm Figure 5. Motion Release Cable Installation (Optional) 3. Leave enough slack in the cable to allow the Type N551 slowly, packing replacement (refer to Type N551 lever to move freely but not close during normal hose Packing Removal/Replacement Instruction Manual, movement or hook-up.
  • Page 7 8 TO 9 FT-LBS / 10.8 TO 12.2 N•m TORQUE: 40 TO 55 FT-LBS / 54.2 TO 74.6 N•m FOR TYPE N551-10 50 TO 60 FT-LBS / 67.8 TO 81.3 N•m FOR TYPE N551-16 ERAA06717_AC APPLY LUBRICANT (L) OR SEALANT (S)
  • Page 8: Parts List

    For further information visit www.fisherregulators.com The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls International LLC, a business of Emerson Process Management.

This manual is also suitable for:

N851-10N851N851k-10N551-16N551-10N551-24 ... Show all