Kohler PowerWAVE 9500DPA User Manual page 79

(100–500 kva/kw) parallelable up to 3 mva/mw
Table of Contents

Advertisement

Terminal
Contact
INPUTS
X3/14
Gnd
X3/13
In
X3/12
Gnd
X3/11
In
X3/10
Gnd
X3/9
In
X3
X3/8
Gnd
X3/7
In
X3/6
Out
X3/5
Gnd
X3/4
Gnd
X3/3
In
X3/2
X3/1
OUTPUTS
X2/18
Com
X2/17
NC
X2/16
NO
X2/15
Com
X2/14
NC
X2/13
NO
X2/12
Com
X2/11
NC
X2/10
NO
X2
X2/9
Com
X2/8
NC
X2/7
NO
X2/6
Com
X2/5
NC
X2/4
NO
X2/3
Com
X2/2
NC
X2/1
NO
CASTELL INTERFACE
X1/2
230Vac
X1
X1/1
N
TS_622_02 PowerWAVE 9500DPA User Manual 26/2/19
Signal
Display
Gnd
Battery Temperature Sensing
(If connected this input is battery temperature dependent)
+3.3V
Gnd
GENERATOR
Customer Specific Input (1)
OPER ON
(Default NC = Generator on line)
+12V
Gnd
Parallel Switch
External output circuit breaker
OPEN/CLOSED
(When used, both the external and the internal (IA2) output breakers
+12V
have to be either open or closed in order to isolate or connect the output
of UPS)
Gnd
EXT MAN BYP
External Manual Bypass
(External IA1)
+12V
+12V
+12Vdc Power source (max 200mA load)
Gnd
Gnd
REMOTE
RSD Remote Shut Down
SHUTDOWN
Leave jumper JP5 in place if no Remote Shut Down input is connected
+12V
REMOTE
RSD Remote Shut Down (For external switch)
SHUTDOWN
Max 250VAC/8A, 30VDC/8A, 110VDC/0.3A, 220VDC/0.12A
Spare
Common
function
Auxiliary NO
Auxiliary NC
Alarm
COMMON
Common
ALARM
No Alarm Condition
Common (System) Alarm active
Status
LOAD ON
Common
MAINS
No Load On Bypass
Load on Bypass (Mains) active
Alarm
BATT LOW
Common
Battery OK
Battery Low active
Status
LOAD ON INV
Common
Load not On Inverter
Load on Inverter active
Alarm
MAINS OK
Common
Mains Failure
Mains Present
EXT MAN BYP
Castell Interlock Function
External Manual Bypass closed (230VAC 2AT)
Figure 9.3 Dry port connection details
Function
:
71