Connecting the 24 V DC supply voltage
The supply voltage is fed in via a 5-pole detachable termi-
nal block.
Important:
Plug and unplug terminal block only with power off!
4
24V DC–IN max. 2,5 W
L+
L+
M
15 16 17 18 19
Terminal assignment:
15
L+ *) Supply voltage +24 V DC
16
L+ *) Supply voltage +24 V DC
17
M
*) Reference potential (0V)
18
M
*) Reference potential (0V)
19
PE
Protective Earth terminal,
connected with the Faston terminal
inside the device.
Do not cause earth loops!
Connect PE and Faston to the
same earthing potential!
*)
Exclusively for connection to the AC31 basic
unit (see also Figure 7.2-6)
Fig. 7.2-4:
Assignment of the terminal block
for the 24 V DC-IN supply voltage
2
07 MK 92 R1161
Supply voltage
Signal name
M PE
Terminal number
7.2.3.3
Electrical isolation and notes on earthing
The following illustration shows which circuit parts of the
unit are electrically isolated from each other and which
internal connections exist. Here, both the clearances and
creepage distances and also the test voltages used cor-
respond to DIN/VDE 0160.
The unit is connected via the 6.3 mm Faston terminal (bot-
tom left) to the functional earth (switch-gear cabinet earth)
via a wire with a cross section of 6 mm
Fig. 7.2-6).
PGND
3
6 mm
2
cross section
Connect to the
Faston of the
basic unit (see
Figure 7.2-6)
Fig. 7.2-5: Electrical isolation and notes on earthing
7.2-6
Hardware
(also see
2
COM5
PE
PGND
24V
COM6
DC-IN
Advant Controller 31 / Issued: 10.99