Operation Command - Omron G3ZA User Manual

Multi-channel power controller
Hide thumbs Also See for G3ZA:
Table of Contents

Advertisement

Operation Command

3-6

Operation Command

Command
Response
■ Response Code
Response code
"1001"
"1002"
"1101"
"110B"
"1100"
"2203"
"0000"
Example: The following command reads the control variable for channel 1
(set value: 8 digits).
Command: [STX]010000101C00001000001[ETX][BCC]
Response: [STX]0100000101000000000000[ETX][BCC]
Example: The following command reads the control variable for channel 1
(set value: 4 digits).
Command: [STX]010000101800001000001[ETX][BCC]
Response: [STX]010000010100000000[ETX][BCC]
This command is used to start and stop operation, save the manipulated vari-
able, execute a software reset, or initialize settings.
Operation
Related
SRC
code
information
MRC
"30"
"05"
2
2
2
MRC
SRC
Response code
"30"
"05"
2
2
4
Error name
Command length too long
Command length too short
Area type error
Response length too long
Parameter error
Operation error
Normal end
2
Section 3-6
Cause
The command is too long.
The command is too short.
The specified variable type
does not exist.
The number of elements is
larger than the maximum
number allowed.
The bit position specification
is not "00".
An error occurred in nonvola-
tile memory.
Processing was completed
normally.
19

Advertisement

Table of Contents
loading

Table of Contents