Communications Specifications

1-3
Communications Specifications
Item
Interface
Communications method
Synchronization method
Baud rate
Transmitted code
Error detection
Transmission control
Transmission distance
8
with 3G2A9-AL002-E or 3G2A9-AL002-PE Link Adapters, the 3G2A9-AL004-E
or 3G2A9-AL004-PE Link Adapter would be replaced with a 3G2A9-AL004-E or
3G2A9-AL004-PE
3G2A9-AL004-PE Link Adapters would be inserted before each PC to convert
back to wire cable. The maximum transmission distance varies with the Link
Adapter and the kind of optical fiber cable as follows:
Cable
APF
20 m
PCF
200 m
APF: all-plastic fiber; PCF: plastic-clad fiber
The specifications of the host interface on the PC's CPU are as follows:
Communications method
Synchronization method
Baud rate
Transmitted code
Error detection
Interface
Transmission distance
The following are the communications specifications of the Host Link Unit. (The
general specifications of the Host Link Unit are the same as those of the CV-se-
ries PCs.)
Port 1
RS-232C
Half duplex or full duplex; Set in CPU Bus
Unit System Setup.
Start-stop, 1 or 2 stop bits; Set in CPU Bus
Unit System Setup.
1200, 2400, 4800, 9600, or 19200 bps; Set
in CPU Bus Unit System Setup.
7- or 8-bit ASCII; Set in CPU Bus Unit
System Setup.
Vertical parity, even/odd/none; Set in CPU
Bus Unit System Setup. FCS (frame
checksum sequence)
Xon/Xoff control; Set in CPU Bus Unit
System Setup.
15 m max.
Link
Adapter
and
3G2A9-AL002-PE
3G2A9-AL004-PE
Connection impossible
800 m
Four-wire, half duplex
Start-stop, 1 or 2 stop bits (set in PC Setup)
1200/2400/4800/9600/19200 bps (set in PC Setup)
7- or 8-bit ASCII (set in PC Setup)
Vertical parity, even/odd (set in PC Setup)
RS-232C/RS-422 (set on selector on CPU)
RS-232C: 15 m max.; RS-422: 500 m total max.
(See details under System Configuration.)
RS-232C or RS-422 (selectable)
RS-232C: Half duplex or full duplex; Set in
CPU Bus Unit System Setup.
RS-422: Full duplex
Start-stop, 1 or 2 stop bits; Set in CPU Bus
Unit System Setup.
1200, 2400, 4800, 9600, or 19200 bps; Set
in CPU Bus Unit System Setup.
7- or 8-bit ASCII; Set in CPU Bus Unit
System Setup.
Vertical parity, even/odd/none; Set in CPU
Bus Unit System Setup. FCS (frame
checksum sequence)
Xon/Xoff control; Set in CPU Bus Unit
System Setup.
RS-232C: 15 m max.;
RS-422: 500 m total max.
Section 1-3
then
3G2A9-AL004-E
3G2A9-AL002-E
3G2A9-AL004-E
Port 2
or

Advertisement

Table of Contents
loading