KNX
Parameters
7.11.1.5.5
Dependent parameter
Send status value
Options:
After a change: Sends the value only after a change.
After a change and cyclically: Sends the value after a change, and cyclically. Displays the dependent
parameters Telegram is repeated every and On object value.
Cyclic sending
Cyclic sending enables the Switch group object to send automatically at a fixed interval. If cyclic sending
applies to a specific object value only (ON or OFF), this condition refers to the value of the group object.
It is therefore possible in principle to start cyclic sending by sending a value to the Switch group object.
As this behavior is unwanted, the Write and Update flags of the group object are deleted in the
preliminary setting so that they cannot be changed via the bus. If this functionality is required
irrespectively, set these flags accordingly. When the group object Switch changes and after bus voltage
recovery (after the sending delay time has elapsed), the group object value is sent immediately on the
bus, and the sending cycle time restarts.
7.11.1.5.5.1
Dependent parameter
Telegram is repeated every
Options:
This additional parameter sets the interval for cyclic sending.
7.11.1.5.5.2
Dependent parameter
On object value
Options:
1: Sends the group object value 1 cyclically.
0: Sends the group object value 0 cyclically.
0 or 1: Sends the group object values 0 or 1 cyclically.
194 2CDC508220D0211 Rev. A | VC/S 4.x.1
After a change
After a change and cyclically
Note
00:00:30...18:12:15 hh:mm:ss
0
1
0 or 1