Location; Generator; Transfer Switch; Battery Installation - Generac Power Systems 04679-1 Installation And Owner's Manual

Air-cooled, prepackaged automatic standby generator
Table of Contents

Advertisement

Figure 1.3 – Demand Regulator (7 kW)
FUEL HOSE
BRASS HOSE
FITTING
HOUSING
PORTS
NG FUEL SYSTEM
8. Refit the brass hose fittings to the outlet port of
the demand regulator.
9. Reverse procedure steps 1-4 to reinstall demand
regulator.
10. Reverse the procedure to convert back to natural
gas.
The natural gas adjustment screw is preset during
installation and should not need any further
adjustment.
1.9

LOCATION

1.9.1 GENERATOR

Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available. Consider these factors:
• Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drift-
ing, consider using windbreak to protect the unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to
allow three feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings to
the prevailing winds.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
• Install the generator as close as possible to the
transfer switch. HOWEVER, REMEMBER THAT
LAWS OR CODES MAY REGULATE THE DIS-
TANCE.
• This genset must be installed on a level surface.
The base frame must be level within 1/2 inch all
around.
FUEL HOSE
BRASS HOSE
FITTING
FUEL JET
HOUSING
PORTS
LP FUEL SYSTEM
NOTE:
Section 1 — General Information
Air-cooled 7 kW Generator

1.9.2 TRANSFER SWITCH

1.9.2.1 7 kW Unit
The transfer switch shipped with this generator is
enclosed in a NEMA 1 enclosure. This type of enclo-
sure is intended for indoor use only. Follow these
rules:
• Install the transfer switch indoors on a firm, stur-
dy supporting structure.
• To prevent switch distortion, level the switch if
necessary. This can be done by placing washers
between the switch enclosure and mounting sur-
face.
• Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
• Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and cor-
rosive vapors.

1.10 BATTERY INSTALLATION

Fill the battery with the proper electrolyte fluid if nec-
essary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF .
2. Turn off utility power supply to the transfer
switch.
If the AUTO/OFF/MANUAL switch is not set to
its OFF position, the generator can crank and
start as soon as the battery cables are connect-
ed. If the utility power supply is not turned off,
sparking can occur at the battery posts and
cause an explosion.
Battery cables were factory connected at the genera-
tor (Figure 1.4). Connect cables to battery posts as
follows:
3. Remove the 5A and 15A fuses from the generator
control panel.
4. Connect the red battery cable (from starter con-
tactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a nega-
tive, NEG or (—).
Damage will result if battery connections are made
in reverse.