General Information; Range Of Application - Siemens 3AH3 Operating Instructions Manual

Vacuum circuit-breaker
Hide thumbs Also See for 3AH3:
Table of Contents

Advertisement

General information

Intended use
Siemens Parts
9229 9860 176 0E
2013-08-22
WARNING
Dangerous voltage and mechanical movements
When operating electrical devices, certain parts will always be live, and
mechanical parts may move very quickly, even when remotely controlled.
If the warnings are not observed, serious injury or damage to material may be the
result.
Only personnel with the relevant qualifications may work on or in the vicinity of
this device. These personnel must be familiar with all the warnings and servicing
measures specified in these operating instructions.
Smooth and safe operation of this device requires proper transport and storage, and
professional installation and assembly, as well as careful operation and mainte-
nance.
The basic version and all listed configurations of the vacuum circuit-breakers are
type-tested devices as per IEC.
Note
In the event of subsequent attachments or integrations, e. g. locking parts in con-
nection with switchgears, ensure that
fast-moving parts are not additionally loaded with mass or force, and
additional parts have sufficient clearance, especially from moving and live
parts.
If vacuum circuit-breakers are to be equipped with additional functions by the cus-
tomer, we recommend consulting the factory, since tried and tested solutions are
frequently available (see also "Additional equipment" on page 23).

Range of application

3AH3 vacuum circuit-breakers are 3-pole interior circuit-breakers for a rated voltage
range of 7.2 kV - 36 kV.
Under normal operating conditions, the vacuum circuit-breaker (as per IEC 62271-1
and VDE 0671-1) is maintenance-free up to 10 000 operating cycles.
3AH3 vacuum circuit-breakers are suitable for switching any type of alternating cur-
rent circuits under normal operating conditions, such as:
Three-phase motors for reversing, turning and direct operation
Transformers
Capacitors
Resistor consumers
Suitable for high frequency of operation and unlimited on-time.
3AH3 vacuum circuit-breakers operate in continuous, periodic and short-term oper-
ation.
General information
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

3ah333ah30

Table of Contents