Since the display screens are identical for each of the Alarms, they
have been combined into one section for the purpose of this manual.
However, each Alarm must be configured separately according to your
specifications.
This option allows you to set minimum and maximum alarm levels for
alarms A, B and C. What this does is set a tolerance range within
which no actions are taken. However, if gas concentrations should go
over the set maximum level, an alarm will be triggered. The alarm will
not be shut off and reset until gas concentrations fall below the
minimum level defined.
Use the keypad arrows to move the cursor arrow to either MIN or
MAX
Press Enter to select the field for modification
Use the keypad up or down arrows to increase or decrease the
value
Press Enter to validate the value.
36
1. Tx Info
1. Tx Info
-Alarm A-
-Alarm A-
MIN
MIN
0.00%
0.00%
301C User Manual
Honeywell
001
001
MAX
MAX
0.00%
0.00%
510324
4/07