Hardware Inputs; Analog; Digital; Hardware Outputs - Siemens 125-5033 Owner's Manual

Two-state constant volume fume hood controller
Table of Contents

Advertisement

Hardware Inputs

Analog

Differential pressure transmitter

Digital

Operator Display Panel (ODP)
ATTN.UNATTN (through DI1)
OCC.UNOCC (through DI1)

Hardware Outputs

Analog
AO-E/AO-P module (Floating Control)
Operator Display Panel (ODP)
AO2 (Flow Signal, 1 to 10 Vdc)
Digital
FLN communications trunk
DO3 (24 Vac, Alarm/Hi.Low Output)

Power Wiring

The controller is powered by 24 Vac. Power wiring connects to the three screw terminals on
the controller labeled "C" (Common), "H" (Hot) and "E" (Ground) on the terminal block labeled
"TB1". Earth ground connection is required (Figure 2).

Communication Wiring

The controller connects to the field panel by means of a Field Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled "+"
(positive), "-" (negative), and "S" (Shield) (Figure 3).
Siemens Building Technologies, Inc.
Product Overview
3