APOGEE Unit Vent
Controller ⎯
0 to 10V Output
Owner's Manual
125-1957
Rev. CA, July 2007
Siemens Building Technologies, Inc.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens 125-1957

  • Page 1 APOGEE Unit Vent Controller ⎯ 0 to 10V Output Owner’s Manual 125-1957 Rev. CA, July 2007 Siemens Building Technologies, Inc.
  • Page 3 Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance.
  • Page 5: Table Of Contents

    Table of Contents How To Use This Manual ... iv Manual Organization ...iv Manual Conventions ... v Manual Symbols ... v Datamate Software ... v Getting Help ...vi Where To Send Comments ...vi Product Overview ... 1 Introduction ... 1 Ordering Notes ...
  • Page 6 APOGEE Unit Vent Controller Point Database ... 23 Troubleshooting ... 33 Overview ... 33 Basic Service Information ... 33 Ordering Replacement Parts... 34 Preventive Maintenance ... 34 Safety Features ... 34 Controller LEDs ... 34 Glossary ... 35 Overview ... 35 0 to 10V Output Owner’s Manual...
  • Page 7 Table of Contents...
  • Page 8: How To Use This Manual

    How To Use This Manual This manual is written for the owner and user of the Siemens Building Technologies, Inc. Unit Vent Controller – 0 to 10V, often referred to as controller for the remainder of this manual. This manual is designed to help you become familiar with the controller and its applications.
  • Page 9: Manual Conventions

    Databases can be saved for permanent storage or used as backup. For more information on Datamate software, refer to the appropriate user guide for the version of Datamate you are using (Base or Advanced), or contact your local Siemens Building Technologies, Inc. representative.
  • Page 10: Getting Help

    APOGEE Unit Vent Controller 0 to 10 V Output Owner’s Manual Getting Help For more information about the Unit Vent Controller, contact your local Siemens Building Technologies representative. Where To Send Comments Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor.us.sbt@siemens.com...
  • Page 11: Product Overview

    Product Overview Introduction The Unit Vent Controller—0 to 10V Output is the Siemens Building Technologies, Inc. Terminal Equipment Controller (TEC) used in unit ventilator applications. See Figure 1. It provides Direct Digital Control (DDC) for five applications. The controller can operate as an independent, stand-alone, DDC room controller or be networked with an APOGEE field panel.
  • Page 12: Hardware Inputs

    DI 2 DI 4 AO 1 AO 2 AO 3 NO C NO C AI 3 TRANSMIT LED TERMINATIONS RECEIVE LED CONTROLLER BOARD MOUNTING HOLE TRUNK MOUNTING RAIL TRUNK ROOM TEMPERATURE SENSOR / MMI PORT BST LED Siemens Building Technologies, Inc.
  • Page 13: Hardware Outputs

    The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. Communication wiring connects to the three screw terminals on the controller labeled “+” (positive), “-“ (negative), and “S” (Shield) (Figure 3). Siemens Building Technologies, Inc. Introduction Application...
  • Page 14: Controller Led Indicators

    Indicates, when flashing, that the controller is transmitting information to the field panel. Indicates, when flashing ON and OFF once per second, that the controller is functioning property. FLN TRUNK (SHIELD) Indication Siemens Building Technologies, Inc.
  • Page 15: Actuators

    • Relay Module • Damper Actuator(s) • Valve Actuator(s) • Mixed Air/Discharge Air Temperature Sensor (optional) • TEC Room Temperature Sensor Contact your local Siemens Building Technologies, Inc. representative for product numbers and more information. Siemens Building Technologies, Inc. Introduction...
  • Page 16: Applications

    The controller maintains the room temperature by resetting the unit ventilator's discharge temperature setpoint (2281/2284), modulating the available coil control device, controlling auxiliary radiation (if provided), positioning the outdoor air or face-bypass damper. Application 2281 Application 2283 Application 2284 Application 2286 Application 2287 Application 2299 Siemens Building Technologies,Inc.
  • Page 17: Valve Configuration

    Room Loop – uses the control setpoint and room temperature to set the discharge setpoint between the minimum and maximum discharge temperature (2281, 2284). Heating Loop – maintains room temperature setpoint by turning valves and/or electric heat stages on and off. Siemens Building Technologies, Inc. Basic Operation...
  • Page 18: Morning Warm-Up/Cool-Down

    Night Mode – The fan only operates when required for heating or cooling. Fail-safe Operation A low temperature detection thermostat (LTDT) can be used to signal the controller when the temperature drops below the low temperature limit. Stage 1 Stage 2 Stage 3 Siemens Building Technologies. Inc.
  • Page 19 Analog and digital outputs cannot be commanded when the controller is in fail-safe mode; however, failed points may be overridden, allowing the controller to return from fail-safe mode. In this instance, room temperature control is not possible. Siemens Building Technologies, Inc. Basic Operation...
  • Page 20: Application 2281 - Heating And/Or Chilled Water Cooling, Ashrae Cycles I And

    FREE CLG (Point 23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate open in sequence with the heating and cooling actuators. The unit ventilator fan is also controlled in this application. Figure 4. Application 2281 Control Drawing. Siemens Building Technologies. Inc.
  • Page 21 Application 2281 – Heating and/or Chilled Water Cooling, ASHRAE Cycles I and II Figure 5. Application 2281 Control Drawing. Figure 6. Application 2281 Control Drawing. Siemens Building Technologies, Inc.
  • Page 22 0 to 10 V Output Owner’s Manual NOTE: The auxiliary radiation is an independent loop and is not sequenced with the other control loops. Figure 7. Application 2281 Control Drawing. Figure 8. Application 2281 Control Drawing. Siemens Building Technologies. Inc.
  • Page 23: Application 2283 - Heating And/Or Chilled Water Cooling, Ashrae Cycle Iii

    The unit ventilator fan is also controlled in this application. Siemens Building Technologies, Inc. Chilled Water Cooling, ASHRAE Cycle III Figure 9. Application 2283 Control Drawing.
  • Page 24 ⎯ APOGEE Unit Vent Controller 0 to 10 V Output Owner’s Manual Figure 10. Application 2283 Control Drawing. Figure 11. Application 2283 Control Drawing. Siemens Building Technologies. Inc.
  • Page 25 Application 2283 – Heating and/or Chilled Water Cooling, ASHRAE Cycle III Figure 12. Application 2283 Control Drawing. Figure 13. Application 2283 Control Drawing. Siemens Building Technologies, Inc.
  • Page 26: Application 2284 - Heating And Dx Cooling, Ashrae Cycles I And Ii

    DX. The unit ventilator fan is also controlled in this application. Figure 14. Application 2284 Control Drawing. Siemens Building Technologies. Inc.
  • Page 27 NOTE: The auxiliary radiation is an independent loop and is not sequenced with the other control loops. Siemens Building Technologies, Inc. Application 2284 – Heating and DX Cooling, ASHRAE Figure 15. Application 2284 Control Drawing. Figure 16. Application 2284 Control Drawing.
  • Page 28: Application 2286 - Heating And Dx Cooling, Ashrae Cycle Iii

    23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate to maintain the mixed air temperature setpoint. The unit ventilator fan is also controlled in this application. Figure 17. Application 2286 Control Drawing. Siemens Building Technologies. Inc.
  • Page 29 Application 2286 - Heating and DX Cooling, ASHRAE Cycle III Figure 18. Application 2286 Control Drawing. Figure 19. Application 2286 Control Drawing. Siemens Building Technologies, Inc.
  • Page 30: Application 2287 - Heating And Cooling, Nesbitt Cycle W

    Nesbitt Cycle W. The free- cooling/economizer function is turned on and off by the field panel using FREE CLG (Point 23). The unit ventilator fan is also controlled in this application. Figure 20. Application 2287 Control Drawing. Siemens Building Technologies. Inc.
  • Page 31 Application 2287 – Heating and Cooling, Nesbitt Cycle W Figure 21. Application 2287 Control Drawing. Figure 22. Application 2287 Control Drawing. Siemens Building Technologies, Inc.
  • Page 32: Application 2299 - Slave Mode

    (CTLR ADDRESS, APPLICATION, etc.). NOTE: Slave mode provides no control. The input labeled "DI3/AI3" on the controller can be used either as a DI point or as an Analog Input (AI) point, but not both at the same time. Siemens Building Technologies. Inc.
  • Page 33: Point Database

    ROOM TEMP HEAT.COOL DAY CLG STPT DAY HTG STPT NGT CLG STPT NGT HTG STPT OADPR MINPOS Siemens Building Technologies, Inc. Table 3. Point Database. Application 2281, 2283, Identifies the controller on the FLN trunk. 2284, 2286, 2287, 2299 2281, 2283,...
  • Page 34 2284, 2286, physically available on all temperature sensor models) at the 2287, 2299 room temperature sensor. ON indicates that the switch is being pressed. OFF indicates that the switch is released. Valid input: ON or OFF Description Siemens Building Technologies, Inc.
  • Page 35 LOW TEMP DET DX COOLING ELEC.NOELEC FBP.2PSVCTL DAY.NGT WRMUP.COOLDN Siemens Building Technologies, Inc. Application 2281, 2283, The amount of time (in hours) that the controller will operate in 2284, 2286, day mode, when the override switch is pressed, while the 2287 controller is in night mode.
  • Page 36 The actual status of the two -position heating valve. 2284, 2286 2299 Digital output 4 controls a 24 Vac load with an ON or OFF status. 2281, 2283 The actual status of the two -position cooling valve. Description Siemens Building Technologies, Inc.
  • Page 37 NGT CLG MODE AUX OUTPUT AUX HTG TIME EHT STG DELY DO DIR.REV HTG OUTPUT Siemens Building Technologies, Inc. Application 2284, 2286, The actual status of the DX cooling compressor. 2287 2287, 2299 Digital output 5 controls a 24 Vac load with an ON or OFF status.
  • Page 38 The minimum time, in minutes, which the unit ventilator's 2287 compressor will remain ON before turning OFF again. Valid input: 0 - 255 minutes 2281, 2284 The control loop output value that is used to determine AUX OUTPUT (Point 55). Description Siemens Building Technologies, Inc.
  • Page 39 OA D GAIN AUX BIAS MA BIAS OA BIAS SWITCH LIMIT SWITCH TIME Siemens Building Technologies, Inc. Application 2283, 2286 The mixed air control loop output value that is used to determine OA DMPR POS (Point 62). 2287 The outdoor air damper control loop output valve that is used to determine OA DMPR POS (Point 62).
  • Page 40 The time, in seconds, between control loop calculations. 2284, 2286, 2287 2281, 2283, The status code indicating any errors detected during controller 2284, 2286, power up. A status of 0 indicates there are no problems. 2287, 2299 Description Siemens Building Technologies, Inc.
  • Page 41: Troubleshooting

    This chapter describes corrective measures you can take should you encounter a problem when using a Unit Vent Controller. You are not required to do any controller troubleshooting. You may want to contact your local Siemens Building Technologies representative if a problem occurs or you have any questions about the controller. NOTE: When troubleshooting, record what the problem is and what actions were performed immediately before the problem occurred.
  • Page 42: Ordering Replacement Parts

    LEDs located on the circuit board. See the Controller LED indicators section of Chapter 1, Product Overview for more information about LEDs. NOTE: The TX and RX LEDs indicate communication over the FLN. 540-509 550-509 ) at the field panel. Siemens Building Technologies, Inc.
  • Page 43: Glossary

    APOGEE Automation System, see the Siemens Building Technologies Technical Glossary of Building Controls Terminology and Acronyms, (125-2185). This book is available from your local Siemens Building Technologies representative. Analog Input. Physical point which accepts a continuous variable signal.
  • Page 44: English Units

    Revised acronym for Floor Level Network. The term “Floor” is no longer used and has been replaced with “Field”. Ioopout Output of the control loop expressed as a percentage. OFF text Text indicating the de-energized state of a digital point (for example, OFF, CLOSED, NO). Siemens Building Technologies, Inc.
  • Page 45 Type of control offered by a controller that is providing independent DDC control to a space. Terminal Equipment ControIler Siemens Building Technologies product family of equipment controllers (one is the Unit Vent Controller — 0 to 10V Output) that house the applications software used to control terminal units, such as heat pumps, VAV terminal boxes, fan coil units, unit ventilators, etc.
  • Page 46 0 to 10V Output Owner’s Manual unbundle Term used to describe the entering of a point that resides in a controller's database into the field panel's database so that it can be monitored at or controlled from the field panel. Siemens Building Technologies, Inc.
  • Page 47 ... 3, 4 control loop ... 33 controller LEDs/LED indicators ... 4, 32 controller hardware ... 1 Siemens Building Technologies, Inc. damper actuator ... 5 database ... (see point database) Datamate Software ... v DDC ... (see Direct Digital Control) DI ...
  • Page 48: Safety Features

    Terminal Equipment Controller ... 35 troubleshooting ... 31 basic service information... 31 TX LED ... 32 unbundle ... 36 Unit Vent Controller ... 1 valve actuator ... 5 wiring communication wiring ... 3, 4 power wiring ... 3, 4 Siemens Building Technologies, Inc.