Apogee unit vent controller ⎯ 0 to 10v output
Table of Contents

Advertisement

APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor
Address
RM STPT MIN
11
RM STPT MAX
12
RM STPT DIAL
13
STPT DIAL
14
AUX TEMP
15
DISCH TEMP
15
MA TEMP
15
1 VLV HTGCLG
16
FBP.MODVALVE
17
WALL SWITCH
18
DI OVRD SW
19
24
Application
2281, 2283,
The minimum temperature setpoint in degrees that the
2284, 2286,
controller can use from the setpoint dial. This overrides any
2287
temperature setpoint from the setpoint dial that falls below this
minimum.
Valid entry range: 48° to 95°F (9° to 35°C)
2281, 2283,
The maximum temperature setpoint in degrees that the
2284, 2286,
controller can use from the setpoint dial. This overrides any
2287
temperature setpoint from the setpoint dial that rises above this
maximum.
Valid entry range: 48° to 95°F (9° to 35°C)
2281, 2283,
The temperature setpoint in degrees from the room temperature
2284, 2286,
sensor (not available on all temperature sensor models). This
2287, 2299
setpoint will be used for control in day mode (heating or cooling)
when enabled by STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9° to 35°C)
2281, 2283,
YES indicates that there is a room setpoint dial on the room
2284, 2286,
temperature sensor and it is to be used as the temperature
2287
setpoint for control in day mode. NO indicates that the
appropriate preset setpoint (Points 6, 7, 8 or 9) will be used as
the temperature setpoint for control in day heating or cooling
mode.
Valid input: YES or NO
2299
Actual reading from a 100K ohm thermistor connected to the
controller's Al 3 input. When a thermistor is connected at Al 3,
DI 3 is not available. Refer to Dl 3 (Point 25).
2281, 2284,
Actual reading from a 100K ohm thermistor connected to the
2287
controller's AI 3 input. When a thermistor is connected at Al 3,
DI 3 is not available. Refer to DI 3 (Point 25).
2283, 2286
Actual reading from a 100K ohm thermistor connected to the
controller's Al 3 input. When a thermistor is connected at Al 3,
DI 3 is not available. Refer to DI 3 (Point 25).
2281, 2283
YES indicates that there is one valve controlling one coil which
may have hot or chilled water in it. (2-pipe heat/cool). NO
indicates any other hardware setup.
Valid input: YES or NO
2281, 2283,
FBP indicates that both heating and cooling will be modulated
2284, 2286
with a face-bypass damper. VALVE indicates all other
configurations.
Valid input: FBP or VALVE
2281, 2283,
YES indicates that the controller is to monitor the status of a
2284, 2286,
wall switch that is connected to DI 2. NO indicates that the
2287, 2299
controller will not monitor the status of a wall switch, even if one
is connected.
Valid input: YES or NO
2281, 2283,
Actual indication of the status of the override switch (not
2284, 2286,
physically available on all temperature sensor models) at the
2287, 2299
room temperature sensor. ON indicates that the switch is being
pressed. OFF indicates that the switch is released.
Valid input: ON or OFF