Morning Warm-Up/Cool-Down; On/Off Coil Valve Control; Electric Heat; Fan Operation - Siemens 125-1957 Owner's Manual

Apogee unit vent controller ⎯ 0 to 10v output
Table of Contents

Advertisement

APOGEE Unit Vent Controller
Cooling Loop – maintains room temperature setpoint by turning valves on and off and using
free cooling (mixed air control) when available.
Auxiliary Loop – modulates the auxiliary loop using the auxiliary setpoint and discharge
setpoint (2284).
Mixed Air Loop – modulates the mixed air loop using the mixed air setpoint and mixed air
temperature (2283).
DX Loop – modulates the cooling loop using the control setpoint and room temperature
(2284).

Morning Warm-up/Cool-down

Morning warm-up or cool-down occurs after the controller switches from night mode to day
mode, upon power-up, or if the controller is reset. During morning warm-up or cool-down, the
controller provides maximum heating or cooling with the outdoor air damper closed until the
temperature of the space reaches setpoint.

ON/OFF Coil Valve Control

When a face-bypass configuration is used, the coils may be turned on and off with two-
position valves using DOs.

Electric Heat

If electric heat is used, it is controlled as follows:
HTG OUTPUT
(Point 60)
0% to 33%
34% to 66%
67% to 100%
In addition, no stage may turn on or off until the time delay has elapsed. Stage one will
always be the first stage to turn on and the last stage to turn off.

Fan Operation

Day Mode – The fan is on all the time.
Night Mode – The fan only operates when required for heating or cooling.

Fail-safe Operation

A low temperature detection thermostat (LTDT) can be used to signal the controller when the
temperature drops below the low temperature limit.
8
0 to 10 V Output Owner's Manual
Stage 1
Stage 2
ON
ON
ON
Stage 3
OFF
OFF
ON
OFF
ON
ON
Siemens Building Technologies. Inc.