Csc Address (Customer Support Center) - Siemens sipart ps2 Operating Instructions Manual

Electropneumatic positioner
Hide thumbs Also See for sipart ps2:
Table of Contents

Advertisement

Operating instructions
Fault description (symptoms)
The two piezo valve constantly
switch alternately in stationary au-
tomatic mode (constant setpoint),
actuator oscillates around a
middle point
SIPART PS2 does not drive the
valve up to the end stop (at
20 mA)
Table 4
Fault description (symptoms)
Zero point shifts sporadically
(> 3 %)
Device function breaks down
Device function breaks down
totally: no display
Table 5
1)

CSC Address (Customer Support Center)

Siemens Production
Automatisation S. A. CSC
1, chemin de la Sandlach
B. P. 189
F--67506 Haguenau CEDEX
-- France --
Tel. 0033--38890--6677
Fax 0033--38890--6688
e-mail: Hotline.ADPA1--2@khe.siemens.de
66
Possible cause(s)
Static friction on the packing glands
of the fittings or actuator too high
Play in the positioner, actuator,
fittings system
Actuator too fast
Supply pressure too low
Load of the supply controller or
system output too low; required
load potential.
Possible cause(s)
Such high accelerations have oc-
curred through impact or shock that
the friction clutch has shifted (e.g.
through steam jets in the steam pipe-
lines)
Insufficient electrical supply
With very high continuous stresses by
vibrations, the following can occur:
Screws of the electrical terminals can
loosen
The electrical terminals and/or elec-
tronic modules can be shaken loose
Corrective actions
Reduce static friction or increase
dead zone of SIPART PS2
(parameter dEbA) until the
oscillating movements stop.
Linear actuator:
Check seating of the stub screw of
the coupling wheel
Rotary actuator:
Check seating of the lever on the
positioner shaft
Correct any other play between the
actuator and fittings
Increase positioning times by
means of restrictor screws
If fast positioning times are
required, increase dead zone
(parameter dEbA) until the
oscillating movements stop.
Increase supply pressure
Intermediate burden converter
Select 3/4 wire operation
Corrective actions
Shut off the cause of the shocks
Reinitialize the positioner
1)
Upgrade at CSC
: mount reinforced
friction clutch (order number
C73451-A430-D14)
Check electrical supply
Tighten screws and secure with seal-
ing varnish
1)
Repair at CSC
Prevention: Mount the SIPART PS2
on rubber metal
A5E00074600-05