Download Print this page
White Rodgers 2B61 Installation Instructions
White Rodgers 2B61 Installation Instructions

White Rodgers 2B61 Installation Instructions

Remote bulb thermostats

Advertisement

Available languages

Available languages

Quick Links

WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
Type 2B61 and 2B62 Remote Bulb Thermostats are designed
for use on a wide variety of heating equipment and appliances,
and are especially suitable for electric heating. Extremely com-
pact in size, these snap-action thermostats are suitable for use
on both inductive and non-inductive loads.
When the temperature of the liquid or air surrounding the bulb
rises, the switch contacts open to turn off the heat. When the
temperature drops the contacts close to turn on the heat.
All wiring must conform to local and national electrical codes and
ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
Switch Action: Open on rise, snap-action
Contact Structure:
Type 2B61: – Single Pole
Type 2B62: – Double Pole
Maximum Ambient:
Temperature Switch: 150°F (66°C)
NOTE
These controls have been accurately calibrated at the factory.
Any attempt to calibrate these controls voids the White-Rodgers
warranty.
The switch mechanism of this control may be mounted in any
location, provided that the temperature and humidity of the air in
which it is located do not cause a condensation on the switch
parts.
If the equipment manufacturer has made provisions for location
of the switch and control bulb, follow his instructions. If none are
provided, the following general rules should be observed:
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, Fax (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
TYPE 2B61 & 2B62
REMOTE BULB THERMOSTAT

INSTALLATION INSTRUCTIONS

To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box, until installation is complete.
Electrical Rating
NON-INDUCTIVE
TYPE
RATING
NUMBER
120V
2B61
25A
2B61
1. The control bulb should be located in an area of average
temperature of the medium being controlled.
When used to sense air temperature (as in an electric
heater) the bulb should be located so that the return air to the
heater flows freely over the bulb. The bulb should be fas-
tened away from the cabinet of the heater so that it senses
air temperature, and not cabinet temperature.
When used to control a liquid bath, be sure that the bulb is
fully immersed in the liquid. Also be sure that the bulb is
located where it can sense average temperature of the liquid.
Printed in U.S.A.
SNAP ACTION
DESCRIPTION
PRECAUTIONS
CAUTION

SPECIFICATIONS

INDUCTIVE RATING
FULL LOAD LOCKED ROTOR
240V
120V
240V
120V
25A
10A
6A
60A
25A
10A
6A
60A
INSTALLATION
PART NO. 37-5539A
Replaces 37-9245
240V
36A
36A
9523

Advertisement

loading

Summary of Contents for White Rodgers 2B61

  • Page 1: Installation Instructions

    INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION Type 2B61 and 2B62 Remote Bulb Thermostats are designed for use on a wide variety of heating equipment and appliances, and are especially suitable for electric heating. Extremely com- pact in size, these snap-action thermostats are suitable for use on both inductive and non-inductive loads.
  • Page 2 All wiring should be done in accordance with local and national electrical codes and ordinances. Follow any instructions provided by the equipment manufac- turer. The diagrams shown here represent typical wiring for these controls. TYPE 2B61 TYPE 2B62 BLACK (LINE) BLUE (LOAD) 240V...
  • Page 3 D’INSTALLER ET D’UTILISER LA COMMANDE, VOUS RISQUEZ DE CAUSER DES BLESSURES ET DES DOMMAGES MATÉRIELS. DESCRIPTION Les thermostats de type 2B61 et 2B62 avec capteur à distance sont conçus pour commander divers types d’appareils de chauffage et particulièrement d’appareils à l’électricité. De dimensions réduites, ces thermostats à...
  • Page 4 Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques. Référez-vous aux directives fournies par le fabricant de l’équipement. Les schémas ci-dessous représentent le câblage typique des commandes. TYPE 2B61 TYPE 2B62 NOIR (RÉSEAU) BLEU (CHARGE) 240 V CHARGE RÉSEAU...