SINGLE OR DUAL RUNOUT WITH KICKSTRIP (SEE
FIG. 13)
1.
Drill one
/
-in. hole for attaching runout.
3
16
2.
Cut runout enclosure and kickstrip to desired length; join
with No. 8 sheet metal screws.
3.
Fit runout and kickstrip into slots of 2 end frames.
4.
Hang assembly on wall mounting strip and adjacent to
unit enclosure.
5.
Attach end frame to unit enclosure with one No. 8 sheet
metal screw (field-supplied).
Step 8 — Balance System (see Fig. 14)
1.
Remove construction debris from unit. Remove protec-
tive plastic from thermostat cover.
2.
Units are shipped with plenum damper wide open. Turn
damper adjustment screw clockwise to close damper and
decrease nozzle pressure to design value. Two or three
runs may be necessary to obtain proper balance.
Note that 36SL,SM,SC,ST have different nozzle types.
Maximum allowable plenum pressure is 5-in. wg.
Fig. 12 — Enclosure with Single or Dual Runout
Fig. 13 — Single or Dual Runout (with Kickstrip)
Fig. 14 — Pressure Measurements