4.1 Read access

4.1.1 Operating data read access

3062947_201707

4. Connection to a Modbus network

Via the Modbus interface, it is possible to gain read and write access to the
air handling control unit.
With read access, actual and set values can be checked, subject to
operating mode, via a Modbus network.
The values can be selected with function code 1 (read coils) or function code
3 (read holding register).
The following data is available for read access:
Description
Central fault
External system enable
Hygrostat humidity
Humidifier enable
System status
Operating status
1)
Pump, hot water
Pump, cold water
Heat source demand
Enable or pump HR
Outside/supply air damper
Exhaust/extract air damper
Enable gas valve
Enable or pump, adiabatic cooling
Enable convector heater (WO)
Thermostat, convector heater (WO)
Water supply line drain valve,
adiabatic cooling, open
Pan drain valve,
adiabatic cooling, open
Inlet valve,
adiabatic cooling, open
Supply air temperature
Outside temperature
Room temperature
Extract air temperature
Air quality (mixed gas)
Set room transducer
Indoor air humidity
Relative humidity, extract air
Relative humidity, supply air
Current set value, supply air
temperature
Current set temperature
Current set value, fresh air proportion
Current set speed, supply air fan
Current set speed, extract air fan
Current set value, relative humidity
Current set value, absolute humidity
Icing-up sensor
Actuating signal, heating
Actuating signal, cooling
Actuating signal, HR
Actuating signal, humidifier
Extract air temperature after
humidifier for adiabatic cooling
Actuation signal reheating
Unit
Factor
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
°C
0.1
°C
0.1
°C
0.1
°C
0.1
V
0.1
°C
0.1
%r.h.
0.1
%r.h.
0.1
%r.h.
0.1
°C
0.1
°C
0.1
%
%
0.1
%
0.1
%r.h.
0.1
g/kg
0.1
°C
0.1
%
0.1
%
0.1
%
0.1
%
0.1
°C
0.1
%
0.1
1)
Type
Index
-
Coil
1
-
Coil
2
-
Coil
3
-
Coil
4
-
Coil
5
-
Coil
117
-
Coil
60
-
Coil
18
-
Coil
61
-
Coil
62
-
Coil
63
-
Coil
64
-
Coil
65
-
Coil
87
-
Coil
89
-
Coil
90
-
Coil
91
-
Coil
92
-
Coil
94
Register
1
Register
2
Register
3
Register
4
Register
5
Register
6
Register
7
Register
8
Register
9
Register
10
Register
11
1
Register
12
Register
13
Register
14
Register
23
Register
24
Register
27
Register
28
Register
29
Register
30
Register
31
Register
32
Register
33
7