Connection; Interface Configuration; Portal Connection (Optional) - Wolf WRS-K Installation And Operating Instructions Manual

Modbus interface
Table of Contents

Advertisement

3.3 Connection

3.4 Interface
configuration
3.5 Portal connection
(optional)
6
3. Installation
Connection to the Modbus network is made via the pluggable terminal block:
1:
GND
2:
RX+/TX+
3:
RX-/TX-
1 2 3
If the Modbus interface was supplied fully assembled with the
Note
control unit, it is also already configured. No further settings are
required.
If the interface is retrofitted, it can be configured as follows:
1. Navigate to the main menu with the Esc key on the BMK programming
module.
2. Select menu item Heating contractor with Enter.
3. Enter password "1234" and confirm with Enter.
4. Select menu item Other... with Enter.
5. Navigate to menu item BMS-Protocol with the up/down arrows.
6. Use Enter to highlight the BMS-Protocol and the up/down arrows to select
protocol type Modbus Slave Standard.
The transfer rate is then automatically set to 19200 and the BMS address
to 001.
7. Confirm these entries with Enter.
8. Use Esc to complete the entry and exit the menu item.
The precise procedure for operating the BMK programming
Note
module can be found in the WRS-K installation and operating
instructions.
Other...
BMS-Protocol
>MODBUS Slave Standard
Transfer rate
>19200 (SOLO RS485)
BMS-Address:
VALUE
SAVE
A transfer rate of 9600 and 8N1 (no parity, 1 stopbit) is required for
communication with "Wolf Link pro".
The data described under "Data point list, BMS connection" are of no further
relevance in this case. The "Wolf Link pro" recognises the control unit and
automatically connects all available data points which can be viewed and/or
adjusted via the Wolf portal http://www.wolf-smartset.de.
S-04
001
Esc CANCEL
3062947_201707