Additional Static Resistance - Zt037 Through 061; Additional Static Resistance - Zt078 Through 150 - York ZT SERIES Technical Manual

3 - 12.5 ton packaged rooftop units
Hide thumbs Also See for ZT SERIES:
Table of Contents

Advertisement

Additional static resistance - ZT037 through 061

Size
Model
CFM Cooling only
(tons)
900
1000
1100
037 (3)
ZT
1200
1300
1400
1500
1200
1300
1400
1500
1600
1700
1800
049 (4)
ZT
061 (5)
1900
2000
2100
2200
2300
2400
2500
1. Add these values to the available static resistance in the respective blower performance tables.
2. Deduct these values from the available external static pressure shown in the respective blower performance tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit delivers less CFM during full economizer operation.

Additional static resistance - ZT078 through 150

Size (tons) Model
CFM
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
078 (6.5)
3900
090 (7.5)
102 (8.5)
ZT
4100
120 (10)
4300
150 (12.5)
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
1. Add these values to the available static resistance in the respective blower performance tables.
2. Deduct these values from the available external static pressure shown in the respective blower performance tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Ducted Systems
1
2 3
Economizer
0.05
-0.05
0.05
-0.03
0.04
-0.02
0.04
0.00
0.03
0.01
0.03
0.03
0.03
0.04
-0.01
0.10
-0.01
0.11
-0.01
0.12
-0.01
0.13
-0.01
0.14
-0.01
0.15
-0.02
0.16
-0.02
0.17
-0.02
0.18
-0.03
0.19
-0.03
0.20
-0.04
0.21
-0.04
0.22
-0.05
0.23
1
Cooling only
Reheat coil
0.03
0.07
0.04
0.08
0.06
0.09
0.08
0.10
0.10
0.11
0.12
0.12
0.15
0.13
0.17
0.14
0.20
0.15
0.22
0.17
0.25
0.18
0.28
0.19
0.31
0.20
0.34
0.21
0.38
0.22
0.41
0.24
0.45
0.25
0.48
0.26
0.52
0.27
0.56
0.28
0.60
0.30
0.64
0.31
0.69
0.32
2
4-in. pleated filter
3
0.01
0.00
0.02
0.00
0.03
0.01
0.04
0.01
0.05
0.01
0.07
0.02
0.08
0.02
0.05
0.01
0.06
0.01
0.06
0.02
0.07
0.02
0.08
0.02
0.08
0.03
0.09
0.03
0.10
0.04
0.10
0.04
0.11
0.05
0.12
0.06
0.12
0.06
0.13
0.07
0.14
0.08
2 3
2 3
Economizer
4-in. filter
0.04
0.12
0.10
0.13
0.17
0.14
0.23
0.16
0.29
0.17
0.34
0.19
0.40
0.20
0.45
0.22
0.51
0.26
0.56
0.27
0.61
0.29
0.66
0.32
0.70
0.35
0.75
0.38
0.79
0.41
0.83
0.44
0.87
0.47
0.91
0.51
0.95
0.55
0.98
0.58
1.02
0.62
1.05
0.67
1.08
0.71
5167821-YTG-K-1118
Electric heat kW
6
9
15
0.00
0.00
0.01
0.00
0.00
0.02
0.01
0.01
0.02
0.01
0.01
0.02
0.01
0.01
0.03
0.02
0.02
0.03
0.02
0.02
0.04
0.01
0.01
0.02
0.01
0.01
0.03
0.02
0.02
0.03
0.02
0.02
0.04
0.02
0.02
0.04
0.03
0.03
0.05
0.03
0.03
0.05
0.04
0.04
0.06
0.04
0.04
0.07
0.05
0.05
0.07
0.06
0.06
0.08
0.06
0.06
0.09
0.07
0.07
0.10
0.08
0.08
0.11
Electric heat kW
2
09
18
24
0.05
0.06
0.07
0.06
0.07
0.08
0.07
0.08
0.09
0.08
0.09
0.10
0.09
0.10
0.12
0.10
0.11
0.13
0.12
0.13
0.15
0.13
0.14
0.17
0.15
0.16
0.19
0.17
0.18
0.21
0.19
0.20
0.23
0.21
0.22
0.25
0.23
0.24
0.28
0.25
0.26
0.30
0.28
0.29
0.33
0.30
0.31
0.35
0.33
0.34
0.38
0.35
0.37
0.41
0.38
0.40
0.44
0.41
0.43
0.47
0.44
0.46
0.50
0.47
0.49
0.53
0.50
0.53
0.56
2
20
24
0.01
0.01
0.02
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.07
0.07
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.10
0.11
0.11
2
36
54
0.08
0.10
0.09
0.11
0.10
0.13
0.11
0.14
0.13
0.16
0.14
0.18
0.16
0.20
0.18
0.22
0.20
0.24
0.22
0.26
0.24
0.28
0.26
0.31
0.29
0.34
0.31
0.37
0.34
0.40
0.37
0.43
0.40
0.46
0.43
0.49
0.46
0.53
0.49
0.56
0.53
0.59
0.56
0.62
0.59
0.65
77