Honeywell IntelliPath Series Installation And Setup Manual page 31

High security internet and gsm communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

PROMPTS
Supervision
17
(UL Hi Line Sec)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM.
GSM 24Hr Tst
18
Y/N (N)_
Old Alarm Time
19
10 Minutes_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or IP.
IP Flt Time
20
(01 mins)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM, or GSM.
GSM Flt Time
21
(01 mins)_
NOTE: The next prompt only appears if the Comm Path Choice is IP&GSM.
Notify Panel Of_
22
(Both IP&GSM
Flts)_
4204/
ZONE
OPTIONS
TRIG.
2-4204
• UL Hi
4
4
Line Sec
• 3 Minutes
• 6 Minutes
[Y], [N]
4
4
• 10 Min
4
4
• 15 Min
• 30 Min
• 1 Hr
• 2 Hrs
• 4 Hrs
• 8 Hrs
• 12 Hrs
• 24 Hrs
[00-99]
4
4
[00-99]
4
4
4
4
[Both IP and
GSM Faults]
[Neither
fault]
Section 3: Programming the Communicator
DESCRIPTION
The AlarmNet network must hear at least one
supervisory message from the communicator during this
supervision period; otherwise, AlarmNet notifies the
central station that a communication failure has
occurred. (If the supervision period is changed after
registration, you must re-register the communicator.)
Press the [space] key to scroll through choices.
NOTE: When "UL Hi Line Sec" is selected, a loss of
communications is treated as an alarm condition by the
central station.
UL: Must be set to "UL Hi Line Sec" (200 sec).
If enabled a message is sent every 24 hrs over GSM to
verify proper operation. If it fails, a Periodic Comm Test
Failure message will be sent over Ethernet.
UL: Must be set to "Y".
Sets how long an undeliverable alarm is retried for
delivery to the central station. If the message is not
validated, it is retried until the old alarm time is
reached or the message is validated.
Press the [space] key to scroll through choices.
UL: Must be set to 10 minutes.
In the event there is a loss of contact with the network
over the Ethernet connection, enter the time delay (in
minutes) before the communicator notifies the central
station. IP failure will always be sent to the central
station as Primary Communication Path Failure.
UL: Must be one (01) minute.
In the event the communicator detects a communication
path failure, enter the time delay (in minutes) before the
communicator notifies the central station. A GSM
failure will always be sent to the central station as
Secondary Communication Path Failure.
UL: Must be one (01) minute.
If "Both IP and GSM Faults" is selected, the device will
only notify the control panel if both communication
paths fail, but will always send notification of either
failure to the central station.
NOTE: The fault relay output (if programmed) will be
triggered only if "Both IP and GSM Faults" is selected.
(If the "GSM Fault Time" and "IP Fault Time" options
are set to zero, faults will not be reported.)
Press the [space] key to scroll through choices.
UL: Must be set to "Both IP and GSM Faults".
3-13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Igsmhs4g

Table of Contents