Emerson Fisher Type H800 Instruction Manual

Relief valve

Advertisement

Quick Links

Instruction Manual
Form 5187
March 2009
Type H800 Relief Valve
WaRning
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion, fire and/or
chemical contamination causing property
damage and personal injury or death.
Fisher
relief valves must be installed, operated
®
and maintained in accordance with federal,
state, and local codes, rules and regulations,
and manufacturer's instructions.
if a leak develops or if the outlet continually
vents gas, service to the unit may be required.
Failure to correct trouble could result in a
hazardous condition. Only a qualified person
must install or service the unit
installation, operation, and maintenance
procedures performed by unqualified personnel
may result in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury. Use
qualified personnel when installing, operating,
and maintaining the Type H800 relief valve.
introduction
Scope of the Manual
This manual provides installation, maintenance, and parts
ordering information for the Type H800 relief valve. Information
for other equipment used with this relief valve is contained in
separate manuals.

Product Description

The Type H800 relief valve
(1)
Direct-Operated relief valve. It is used primarily between a
pneumatic instrument and its supply pressure regulator to limit
the instrument supply pressure to 50 psig (3,4 bar) should
the supply pressure regulator fail open. The Type H800 relief
valve can also be mounted on other equipment, such as an air
compressor, where limited relief capacity is desired.
1. Relief valve defined in ANSI Standard B95.1-1972. Not all codes or regulations permit these valves to be used as final overpressure protection devices.
(See Figure 1) is a compact,
www.emersonprocess.com/regulators
W3618
Figure 1. Type H800 Relief Valve
Specifications
Specifications for the Type H800 relief valve are given on
page 2. Additional specifications for 67 Series regulators used
with Type H800 relief valves are shown in Table 1.
installation
Upon receipt, inspect the relief valve to be sure it is free of
foreign material.
WaRning
!
installing a Type H800 relief valve where its
capabilities can be exceeded or where proper
operation might be impaired may cause
personal injury, property damage, or leakage
due to bursting of pressure-containing parts or
explosion of accumulated gas. To avoid such
conditions, install a Type H800 relief valve where:
• Service conditions are within the unit
capabilities are specified in specifications
section and Table 1, and
• The relief valve is protected from
exposure to physical damage and/or
corrosive substances.
Type H800

Advertisement

loading

Summary of Contents for Emerson Fisher Type H800

  • Page 1: Product Description

    Type H800 Instruction Manual Form 5187 March 2009 Type H800 Relief Valve WaRning Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, fire and/or chemical contamination causing property damage and personal injury or death. Fisher relief valves must be installed, operated ®...
  • Page 2: Specifications

    Type H800 Specifications Body Size and End Connection Style Maximum Temperature Capabilities NPS 1/4, NPT (internal) -20° to 150°F (-29° to 66°C) Maximum allowable inlet (Relief) Pressure IEC Sizing Coefficients 250 psig (17,2 bar) : 0.775 Relief Pressure Ranges : 0.50 Non-adjustable, Start-to-discharge between : 0.89 39 and 44 psig (2,7 and 3,0 bar)
  • Page 3 Type H800 PnEUMaTiC aCTUaToR yoKE inSTRUMEnT TyPE 67aFR TyPE H800 REgULaToR RELiEF VaLVE inLET PRESSURE TUBing TUBing FoR VEnT ConnECTion inSTRUMEnT SUPPLy PRESSURE aCTUaToR yoKE W3615 inSTaLLaTion a aCTUaToR yoKE TyPE 67aFR REgULaToR PnEUMaTiC TyPE H800 inSTRUMEnT RELiEF VaLVE PiPE PLUg (May aLSo BE oPTionaL gaUgE) inLET PRESSURE TUBing...
  • Page 4: Parts List

    For further information visit www.emersonprocess.com/regulators The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a business of Emerson Process Management.