Troubleshooting; No Led Light; No Communication; Specification - Raypak BACnet Interface Module Installation And Operation Manual

Adds bacnet mstp capability to temptracker mod+ hybrid controls
Table of Contents

Advertisement

TrOuBLeSHOOTIng

no LeD Lights
• The RJ45 connection to the control powers the BACnet Interface Module. If all LEDs are off, then check the cable
connecting the module to the control. The cable consist of 8 wires. Check each of the color-coded wires continuity in
the cable using a continuity meter.

no Communication

• Check the Yellow and Green LEDs. If the Yellow LED is continuously On or Off, then check the cable connecting the
module to the control.
• If the Green LED is continuously On or Off, then check the cable connecting the module to the BACnet network.
• Make sure that the control's Baud Rate and the BACnet Network's are the same. See "BACnet Baud Rate" on page 5.

SPeCIfICaTIOn

Control Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45 to control (Cable is provided)
BACnet MS/TP Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-wire
Extension Communication. . . . . . . . . . . . . . . . RS485 (RJ11) to Extension (Cable packaged with Extension)
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Red, Yellow, and Green
Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-¾" x 3-⅝" x 1"
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Pound